品牌:RETZ瑞茨/我們一直致力于流體控制領(lǐng)域的持續(xù)創(chuàng)新,始于2005……進(jìn)口燃?xì)饩o急切斷電磁閥在日常工作中處于常開(kāi)狀態(tài),電磁閥線(xiàn)圈處于斷電狀態(tài),不消耗電能 The
gas emergency shut-off solenoid valve is in a normally open state in daily
work, and the solenoid valve coil is in a power off state, without consuming
electrical energy
當(dāng)事故發(fā)生時(shí),系統(tǒng)發(fā)出型號(hào),閥門(mén)線(xiàn)圈瞬時(shí)通電,觸發(fā)閥門(mén)快速關(guān)閉,并進(jìn)入自鎖狀態(tài) When
an accident occurs, the system issues a model number, and the valve coil is
momentarily energized, triggering the valve to quickly close and enter a
self-locking state
當(dāng)工作人員處理完事故,人工重新開(kāi)啟閥門(mén),才會(huì)恢復(fù)供氣 Only
when the staff have handled the accident and manually reopened the valve can
gas supply be restored
閥門(mén)采用先導(dǎo)式閥瓣,開(kāi)啟輕松,即使壓力達(dá)到6Bar開(kāi)啟也十分輕松,口徑大于DN125,采用杠桿手柄,使閥門(mén)達(dá)到開(kāi)關(guān)省力、快捷 The
valve adopts a pilot operated disc, making it easy to open even when the
pressure reaches 6Bar. The diameter is larger than DN125, and a lever handle is
used to make the valve labor-saving and fast to open and close
根據(jù)客戶(hù)要求也可提供斷電關(guān)閉的常閉型緊急切斷閥
According to customer requirements, a normally closed emergency shut-off valve
can also be provided for power-off closure
進(jìn)口燃?xì)饩o急切斷電磁閥控制原理--Control
principle of imported gas emergency shut-off solenoid valve
常開(kāi)--閥關(guān)閉后在通電或斷電都不會(huì)自動(dòng)開(kāi)啟,需手動(dòng)拉開(kāi),保持打開(kāi)狀態(tài),節(jié)能、安全
Normally open - After the valve is closed, it will not automatically open when
powered on or off. It needs to be manually opened and kept open, which is
energy-saving and safe
1.閥需要打開(kāi)時(shí),旋下防護(hù)罩,用力拉手柄,閥打開(kāi) When
the valve needs to be opened, unscrew the protective cover and forcefully pull
the handle to open the valve
2.閥需要關(guān)閉時(shí),線(xiàn)圈通電不超過(guò)30秒鐘,閥迅速關(guān)閉 When the valve
needs to be closed, the coil is energized for no more than 30 seconds and the
valve quickly closes
手動(dòng)復(fù)位操作過(guò)程--
Manual reset operation process
當(dāng)閥門(mén)被切斷,管道漏氣故障排出后,工作人員需要手動(dòng)復(fù)位時(shí),用力向上提拉手動(dòng)復(fù)位桿,聽(tīng)到“咔”的一聲,說(shuō)明閥門(mén)完全被打開(kāi),此時(shí),即使松開(kāi)手,也不會(huì)被切斷。(除非再給閥門(mén)線(xiàn)圈通電)
When
the valve is cut off and the pipeline leakage fault is eliminated, the staff
needs to manually reset it. When they forcefully pull up the manual reset lever
and hear a "click" sound, it indicates that the valve is fully
opened. At this time, even if the hand is released, it will not be cut off.
(Unless the valve coil is energized again)
注:手動(dòng)復(fù)位必須在電磁閥線(xiàn)圈斷電時(shí)操作。
進(jìn)口燃?xì)饩o急切斷電磁閥選型參數(shù)--
閥體材質(zhì):鑄鋼、不銹銹304
閥門(mén)規(guī)格:G1/4-G2"
或F1/2-F8"
工作壓力:0.5bar~6bar
電氣防護(hù)等級(jí):CEIIP65/IP67
防護(hù)性能:防水、防爆(DⅡCT5、ExdⅡCT5、ExmbⅡCT4、ExdⅡCT4)、防腐。
工作電壓及電功率:交流AC220V,50Hz/14V,直流DC12V/8.5W,DC24V/8.5W
操作系數(shù):不間斷輸出或脈沖型
工作環(huán)境溫度:-15~60°C
密封材料:NBR橡膠
閥門(mén)關(guān)閉時(shí)間:少于1秒
適用介質(zhì):煤氣、天然氣、液化氣、朝氣、甲烷、瓦斯等氣體或燃油
進(jìn)口燃?xì)饩o急切斷電磁閥應(yīng)用--
RETZ燃?xì)饩o急切斷閥是新型的燃?xì)夤艿拦こ痰陌踩涮籽b置,主要應(yīng)用于以下場(chǎng)合:
1、與可燃?xì)怏w泄漏監(jiān)測(cè)儀器相連接。當(dāng)儀器檢測(cè)到可燃?xì)怏w泄漏,自動(dòng)快速關(guān)閉主供氣體閥門(mén)。切斷燃?xì)獾墓┙o,及時(shí)制止而惡性事故的發(fā)生。
2、與熱力設(shè)備的極限溫度(或壓力)安全閥控制連接;當(dāng)設(shè)備內(nèi)檢測(cè)點(diǎn)的溫度或壓力超過(guò)設(shè)定的極限數(shù)值時(shí),自動(dòng)快速關(guān)閉供氣閥門(mén),停止燃料的供給。
3、與高層建筑的中央消防報(bào)警系統(tǒng)相連接。當(dāng)大廈發(fā)生火警時(shí),自動(dòng)切斷大廈內(nèi)的燃?xì)夤?yīng),防止煤氣爆炸的發(fā)生。
4、在城市或工廠的燃?xì)夤?yīng)管網(wǎng)內(nèi)設(shè)置BZCK燃?xì)饩o急切斷閥,可在中央控制室內(nèi)集中控制,遠(yuǎn)距離遙控,緊急關(guān)閉事故現(xiàn)場(chǎng)的管線(xiàn)供氣。
5、可靠的技術(shù)性能,極低的負(fù)荷損失,極高的安全性能,極佳的節(jié)能性能,快速切斷性能